Bradford White AeroTherm Series G2 error code 11

Airflow Restriction

What it means

Filter is too dirty to enable proper function of water heater. The evaporator is operating at a colder temperature than the ambient temperature as measured by T5.

Source: Installation and Operation Manual, Hybrid Electric Heat Pump Water Heater, 238-55123-00C (ECO 9059), page 34

Also listed in: Quick Service Guide, Heat Pump Water Heaters AeroTherm Series (Service Manual Supplement), 238-55219-00A, page 1

What Bradford White says to do

Filter must be cleaned when the alarm is displayed. To clean the filter: leave the power ON; pull the filter out of the slot on the air intake; vacuum, wipe clean with a damp cloth, or rinse with warm water; once cleaned and dried, align it into the slot on the top of the unit and push it into place. If the dirty filter alarm returns within a few days after cleaning and resetting, further diagnosis by a service technician is necessary.

Source for these steps: Installation and Operation Manual, Hybrid Electric Heat Pump Water Heater, 238-55123-00C (ECO 9059), page 30

Last checked 2026-10-03.