Bradford White AeroTherm Series G2 error code 6

Supply Voltage Fault

What it means

The voltage is too low at power-up. The control monitors the input line voltage one minute after power-up, and if the voltage is below 155 VAC, the fault code will be displayed.

Source: Installation and Operation Manual, Hybrid Electric Heat Pump Water Heater, 238-55123-00C (ECO 9059), page 34

Also listed in: Quick Service Guide, Heat Pump Water Heaters AeroTherm Series (Service Manual Supplement), 238-55219-00A, page 1

What Bradford White says to do

If a "Fault Code 6" is shown on the display, the water heater is not receiving the correct voltage as a result of incorrect wiring. To correct this fault, turn the power OFF to the water heater, correct the wiring issue, then turn the power back ON.

Source for these steps: Installation and Operation Manual, Hybrid Electric Heat Pump Water Heater, 238-55123-00C (ECO 9059), page 15

Last checked 2026-10-03.